Re: gas / pressure drop when CH fires up |
| message from Andy Hall on 22 May 2004 |
You shouldn't notice a difference really.
The spec is that there should not be more than 1mB of pressure drop as
measured from the meter and then at each appliance with everything
running. Typically it should be 21mB at the meter test point and 20mB
at the test point of each appliance before the regulator.
http://www.cda.org.uk/megab2/build/pub124/sec3.htm#4.3%20Copper%20Tube%20Sizing
gives a bit of background on this.
It is possible that the regulator/governor on the meter is going
faulty. This can happen and mean that it is not maintaining pressure
at the meter end either.
All of this needs to be tested using a manometer or digital pressure
meter to determine what is going on.
For most boilers, unless very large, or the piperun very long, if the
entire run from the meter to the boiler is in 22mm, it should
adequately supply it plus a hob teed off from it.
You can also do a rough theoretical calculation using the info. in the
link above. You willl need to look at the appliance rating
information, work out gas volume and refer to the design guide if you
want to do this.
My money would be on either there not being a problem at all and the
hob is actually OK, pipework inadequate from meter to tee or faulty
meter governor......
In any event it should be checked.
.andy
To email, substitute .nospam with .gl
|
| Andy Hall replied to BigWallop on 22 May 2004 |
There's a bunch of them linked from this page which also deal with how
to size pipes in other applciations
http://www.cda.org.uk/megab2/build/copperin.htm
.andy
To email, substitute .nospam with .gl
|
|
Archived message: Re: gas / pressure drop when CH fires up (UK D-I-Y Home Decoration)