Re: Yet another outdoor power Q |
| message from keith dulwich on 23 May 2004 |
Thanks, the smoke alarms do have battery back up, so moving them to a
lighting circuit seems the best way. I'm surprised that the RCB can be at
the end of the external cable - I naively assumed it neeed to be at the
start in case of faults within the cable - butI suppose that's pretty rare!
So it'll be:
2.5mm2 from spare non-RCB fuse way, metal joint box (inside garage) to
armoured cable, through wall , garden, shed, then a RCB protected socket, on
metal back box to allow termination using proper gland.
|
| Lurch replied to keith dulwich on 23 May 2004 |
That sounds spot on. Although the correct terminology for the socket, for when
you're going to buy one, would be a metal clad RCD protected socket.
|
|
Archived message: Re: Yet another outdoor power Q (UK DIY House Renovation)