| message from Murdo MacKenzie on 17 May 2004 |
The central heating system in my house (a bungalow with a floored loft) has
been plumbed entirely with 15mm plastic barrier piping. While I've never
had a problem with the pipes, I wonder about the use of 15mm for the heating
loop. The loop comes from the boiler and is immediately dropped from 22mm
to 15mm and this feeds 6 radiators of varying sizes. There is also a medium
sized radiator upstairs, in the loft, which is fed directly from the boiler.
I'm about to get the boiler moved from the kitchen to an upstairs cupboard,
but wondered if I'd get better performance from the radiators if the loop
was replumbed to be 22mm all the way.
Any thoughts appreciated.
Thanks,
Murdo
|
| Set Square replied to Murdo MacKenzie on 17 May 2004 |
A lot depends on how it's plumbed. If you have a *single* 15mm loop, with
*all* the radiators dropping off it, that's not likely to be very good. On
the other hand, if you have a "manifold" at the 22mm end - with an
individual 15mm flow and return pipe for each radiator connected into it,
it's probably ok.
There are rules of thumb (which I've forgotten) about how much heat you can
reasonably carry in a 15mm pipe (is it 6kW?) - based on flow and temperature
drop. I suggest that you find them, and check your system for compliance
with them.
If you *have* got a manifold, you will need to use 22mm pipe to extend the
flow and return pipes to it from the new boiler position.
|
| Christian McArdle replied to Murdo MacKenzie on 17 May 2004 |
Well, 15mm is in the same ballpark as 6 radiators, although we can't tell if
it is officially OK without knowing the radiator outputs. Also, the likely
consequences of slight undersizing is a slight increase in noise, or,
alternatively, a slight reduction in performance depending on the pump
setting. The limiting factor here is the speed of water in the pipes, which
should be kept low to avoid noise.
My house had only a 6kW heating requirement via 8 radiators, which could
have marginally been done entirely in 15mm. However, I have run the main
unzoned backbone in 22mm and had the various zones spurred off in 15mm. The
maximum on a zone is around 3kW, around half the allowed figure.
However, the 15mm would not be able to feed a modern hot water cylinder
itself. Hopefully, any hot water circuit would be entirely 22mm.
Christian.
|
|